PLC Programmable logic controller Xinje-XC3-60
36 DI/24 DO, AC220 power supply;can be expanded with external module, BD board;support RTC, power-off retentive;support basic logic control and data operation;support high speed count, pulse output, external interruption, C language function block, free;
switch for I/O points, free protocol communication and MODBUS communication
General Specifications
Item | Specifications |
Insulation Voltage | Above DC 500V 2MΩ |
Noise Resistance | 1000V 1uS pulse for 1 minute |
Environment Temperature | 0~60 |
Ambient Humidity | 5%~95% |
COM 1 | RS-232, be connected to host machine or HMI for programming or debugging |
COM 2 | RS-485/RS-232,network or connect to intelligent instrument, inverter, etc. |
COM 3 | BD board extensional communication port RS-485/RS232 |
Installation | M3 screw fixed or DIN46277 (35mm width) guide rail installation. |
Grounding | The third type grounding (Never perform common grounding with strong power system) |
Functional Specifications
Item | Specification | |
Program Operation Mode | Circulation scanning mode, timing scanning mode | |
Program Mode | Instructions and ladder chart | |
Dispose Speed | 0.5us | |
Power Failure Holding | FlashROM | |
User Program’s Capacity | 8000 steps | |
I/O Points | 28 input points,20 output points. | |
Output Format | Relay | |
Power Supply | AC220V | |
Interior Coil’s Points (M) | 8512 points | |
Timer(T) | Points | 620 points |
Specification | 100mS timer: set time 0.1~3276.7 seconds 10mS timer: set time 0.01~327.67 seconds 1mS timer: set time 0.001~32.767 seconds. | |
Counter(C) | Points | 635 Points |
Specification | 16 bits counter: Set value K0~32767 32 bits counter: Set value K0~2147483647 | |
Data Register(D) | 8512 characters | |
FlashROM Register(FD) | 2048 characters | |
High-speed Count Format | High speed counter, pulse output, exterior interruption | |
Timing Scanning Interval Setting | 1~99mS | |
Password Protection | 6 characters ASCI | |
Self-diagnose Function | Power on self-diagnose, monitor timer, grammar check |